15kVA-60kVA
208/120VAC Three-Phase
Mission Critical Availability while reducing costs with Scalable M90 for 15kVA, 20kVA, 30kVA, 40kVA, 45kVA, 60kVA applications.
The M90 is a scalable modular online UPS that protects critical data and equipment from power problems while supplying clean and reliable network grade power.
The M90 can be configured with a fully redundant power module and battery modules. Should one module fail, the remaining modules smoothly take over the load. Because the power modules are independent, they can be hot swapped without risk to the critical load.
As power requirements change, M90 modularity makes it easy to add modules and increase capacity.
Product Snapshot
MODEL NUMBER | M90-15 | M90-20 | M90-30 | M90-40 | M90-45 | M90-60 | |
---|---|---|---|---|---|---|---|
INPUT | Capacity | 15kVA (13.5kW) | 20kVA (18kW) | 30kVA (27kW) | 40kVA (36kW) | 45kVA (40.5kW) | 60kVA (54kW) |
Nominal | 208/120V 50/60Hz auto sensing | ||||||
Range | 121-253VAC*(L-L) 40-70Hz | ||||||
OUTPUT | Voltage | 208/120VAC | |||||
Frequency | 50/60 ± 0.05Hz | ||||||
THD (full load) | 0.9 | ||||||
Voltage regulation | <2% | ||||||
Efficiency | 98% ECO mode, ≥ 92% online mode | ||||||
Overload capacity | 105%-110% for 60 min;110%-125% for 10min; 126%-150% for 1min; <150% for 200ms | ||||||
BATTERY SYSTEM | Nominal voltage | ±120V | |||||
Temperature compensation | Yes with optional sensor | ||||||
Charging current (programable) | 8A | 16A | 24A | 8A | 16A | 24A | |
PHYSICAL | Enclosure | 20.3″W x 39.4″D x 54″H/484 lbs | |||||
Power module | 19.0”W x 28.0”D x 5.1”H / 74 lbs | ||||||
Battery module | 4.1”W x 28.3”D x 6.0”H / 68 lbs | ||||||
ENVIRONMENT | Temperature | 0–40°C (32–104°F) | |||||
Altitude | 5,200 ft above sea level | ||||||
Audible noise | < 65dBA at 1m | ||||||
APPROVALS | UL-1778 (TUV), cUL, FCC A, RoHS, Energy Star Certified | ||||||
COMMUNICATIONSINTERFACE | RS-232, EPO, intelligent slot for optional cards (Web/SNMP, Relay, Modbus) | ||||||
AVAILABLE OPTIONS | External maintenance bypass, 480V input transformer, output distribution, battery temperature sensor |