Features

Meeting stringent design and performance specifications, the self-diagnostic, self-testing EON is UL 924 listed as “Emergency Lighting Equipment” and “Auxiliary Lighting and Power Equipment”, as well as NFPA compliant as “Life Safety Equipment”. The EON meets NFPA 101, NFPA 111, NEC and IBC requirements, and provides the industry’s most advanced life safety system testing available!

Whether fed from the AC power source or even while in battery mode, the EON has a peak overload capability of 1700% to accommodate inrush current from LED fixtures!

Key EON options include output distribution with either monitored or unmonitored circuit breakers, normally off bus for standby (normally off) emergency light fixtures, and wrap-around maintenance bypass options that include a padlock attachment for lockout / tagout purposes during maintenance. In addition, the optional NetMinder™ provides remote inverter status, monitoring and communications via BACnet, Ethernet, MODBUS TCP, or MODBUS RS485.

The EON model features one of the smallest three phase cabinet footprints in the industry!

  • Input and Output Nominal Voltage: 208/120V, 480/277V, or 600/347V Wye
  • Input Operating Voltage Range: +10%, -15% at full load
  • Input Frequency: 60 Hz, ± 2.5% (50 Hz models available)
  • Input Power Factor Correction: > .98 pF typical, at full load
  • Output Voltage Regulation: ± 3% from nominal, typical
  • Output Frequency: ± 0.5% while in battery operation mode
  • Output Voltage Distortion: Typically 3% output THD with linear load
  • Overload: Up to 110% for 2 minutes, 125% for 30 seconds, 150% for 10 seconds, and 400% for 4 cycles (without use of static bypass)
  • LED Inrush Rating: Peak overload capability of 1700% to accommodate inrush current from LED fixtures (without the use of static bypass)
  • Efficiency: 90% typical
  • Operating Temperature: 20º to 35º C for UL 924 Listed models and C-UL Listed models to CSA C22.2 No. 141-15. UL testing performed at 40º C under full load and at low line input voltage
  • Operating Temperature: 20º (10° optional) to 40º C for C-UL Listed models to CSA C22.2 No. 141-10
  • Optimum Battery Performance and Life: 25º C for both UL and C-UL Listed models
  • Battery Time: UL 924 Listed 90 minutes at full-rated kW output, or with optional runtimes from 15 minutes to 4 hours. C-UL Listed 30 minute runtime to CSA C22.2 No. 141-10; 141-15

Downloads

EON Brochure

EON General Specification 10-33KW

EON General Specification 40-55KW

Contact one of our experienced Sales Professionals for details